Product Catalog
Contact Information
Certificate
Introduction::
Environmental Conditions |
Ambient temperature: -25℃~+60℃ Relative humidity: 30%~85%RH Altitude: ≤2000m
|
Power Supply Conditions
|
Rated voltage: 220V~450V Voltage deviation: ±5% Harmonic voltage: Sine wave, with total distortion rate no more than 5% Working frequency:50HZ
Harmonic current: The allowable harmonic current at the point of common coupling shall not exceed the value required in the standard BG/T14549-1993. Power consumption: <0.2W/1kvar
|
Electrical Safety
|
Electrical clearance, creepage distance, insulation strength, safety protection, short circuit strength, as well as sample circuit protection and control circuit protection conform to the requirements of relevant clauses in the electric power industry standard of the People’s Republic of China DL/T842-2003
|
Measurement Error
|
Voltage: ≤±0.2%; Current: ≤±0.2%; Power: ≤0.2%; Power factor: ±1%; Temperature: ±1℃
|
Protection Error
|
Voltage: ≤0.5%; Current: ≤0.5%; Temperature: ±1℃; Time: ±0.1s
|
Reactive Compensation Parameters
|
Reactive compensation error: ≤50% of the minimum capacitor capacity;
Capacitor switching interval: >10s, to be set between 10-180s; Reactive capacity: 5kvar, 10kvar, 20kvar Networking: ≤32 sets |
Reliability Parameters
|
ontrol precision: 100%; Allowable switching times: 1 million times; Attenuation rate of running time of capacitor capacity: ≦1%/year; Switching attenuation rate of capacitor capacity: ≦0.1%/10,000 times; |
Working Environment
|
Relative humidity: 20%~90%RH @40℃
|
Altitude: ≤2000m
|
Other requirements: free of flammable and combustible medium, conducting dust or corrosive gas.
|
Working Power Supply
|
Working voltage: 380V±20% Frequency: 50Hz Distortion rate of voltage: ≤20%
|
Power consumption: ≤3W
|
Measurement accuracy
|
Voltage: ±0.5%
|
Current: ±0.5%
|
Power factor: ±1%
|
Reactive power: 1%
|
Control accuracy
|
Power factor: ±1%
|
Reactive power: minimum capacitor capacity±120%
|
Compensation Type
|
Model and Specification
|
Overall Dimension (foot stand included) L×W×H (mm)
|
Installation Dimension(mm)
|
Three-phase joint compensation
|
RXZNG/450/10(5+5)
|
400×80×225
|
370×50
|
RXZNG/450/15(10+5)
|
400×80×225
|
370×50
|
|
RXZNG/450/20(10+10)
|
400×80×245
|
370×50
|
|
RXZNG/450/30(15+15)
|
400×80×275
|
370×50
|
|
RXZNG/450/30(20+10)
|
400×80×325
|
370×50
|
|
RXZNG/450/40(20+20)
|
400×80×325
|
370×50
|
|
Split-phase compensation
|
RXZNF/250/5
|
400×80×225
|
370×50
|
RXZNF/250/10
|
400×80×245
|
370×50
|
|
RXZNF/250/15
|
400×80×275
|
370×50
|
|
RZNF/250/20
|
400×80×325
|
370×50
|
YES, I am interested in your product, please contact me!